SMA America, LLC 11 Technical Data
Installation Manual SB6-11TL-US-IA-en-13 83
Grid Connection
Protection Devices
General Data
AC nominal power 11,000 W
Maximum AC power 11,000 W
Reduced power output at 140 °F (60 °C) 8,000 W
Maximum AC current at 240 V AC 48.6 A
Maximum AC reverse current 0 A
Maximum AC fuse size 60 A
AC nominal voltage 240 V
AC voltage range at 240 V AC 211 V to 264 V
AC nominal frequency 60 Hz
AC nominal frequency range 59.3 Hz to 60.5 Hz
Power factor at nominal power 1
Total harmonic factor < 4%
AC connection/Power Balancing Two Phases / ✓
Ground fault monitoring (R-Iso) Yes
Power consumption nighttime ≤ 0.25 W
DC reverse polarity protection Short-circuit diode
AC short-circuit current capability Software-controlled
AC overcurrent protection Current-controlled
Grid monitoring SMA Grid Guard
Topology Transformerless
Cooling concept OptiCool
Protection class NEMA 3R
Optional communication interfaces RS485/wireless (Bluetooth)
DC connection Screw terminals
AC connection Screw terminals