11 Technical Data SMA America, LLC
80 SB6-11TL-US-IA-en-13 Installation Manual
11.5 Sunny Boy 10000TL-US
PV Array Connection
Grid Connection
Maximum DC power 10,350 W
Maximum DC voltage 600 V
Minimum DC voltage at 208VAC 300 V
Minimum DC voltage at 240VAC 345 V
DC nominal voltage at 208VAC 345 V
DC nominal voltage at 240VAC 379 V
DC start voltage 360 V
MPP voltage range at 208 V AC 300 V to 480 V
MPP voltage range at 240 V AC 345 V to 480 V
Maximum DC input current at 208 V AC 35 A
Maximum DC input current at 240 V AC 30 A
Number of MPP trackers 1 (OptiTrac)
AC nominal power 10,000 W
Maximum AC power 10,000 W
Reduced power output at 140°F (60°C) 8,000 W
Maximum AC current at 208 V AC 49 A
Maximum AC current at 240 V AC 48 A
Maximum AC reverse current 0 A
Maximum AC fuse size 60 A
AC nominal voltage 208 V/240 V
AC voltage range at 208 V AC 183 V to 229 V
AC voltage range at 240 V AC 211 V to 264 V
AC nominal frequency 60 Hz
AC nominal frequency range 59.3 Hz to 60.5 Hz
Power factor at nominal power 1
Total harmonic factor < 4%
AC connection/Power Balancing Two Phases / ✓
Ground fault monitoring (R-Iso) Yes
Power consumption nighttime ≤ 0.25 W