SMA America, LLC 5 Electrical Connection
Installation Manual SB6-11TL-US-IA-en-13 33
* only SB 6000TLUS-12/SB 7000TLUS-12/SB 8000TLUS-12/SB 9000TLUS-12/SB 10000TLUS-12/SB 11000TLUS-12
5.4 AC Connection
H Sunny Boy: Output AC line terminals (N, L1 and L2)
IAC varistor terminal with AC varistors
K SMA DC Disconnect: Output AC line terminals (N, L1 and L2)
L SMA DC Disconnect: Grounding electrode terminal for the connection of:
Grounding electrode conductor
DC equipment grounding
AC equipment grounding
M SMA DC Disconnect: DC+ terminal
N SMA DC Disconnect: DC − terminal
ODC varistor terminal with DC varistors*
P Sunny Boy: DC − terminal
Q Sunny Boy: DC+ terminal
R Terminal for optional communication (RS485)
Danger of fire
Overcurrent may lead to a cable fire.
Protect the electrical installation on the AC side. Observe the maximum fuse sizes of the
inverter types (see 11"Technical Data",page70).
Do not connect more than 1 inverter to 1
miniature circuit-breaker..
Install a separate miniature circuit-breaker for
each load. Do not connect any branch circuit
wires to the miniature circuit-breakers.
Electrical Installations
Perform all electrical installations in accordance with all electrical standards applicable locally
and the National Electrical Code
®
(NE, ANSI/NFPA 70).
See National Electrical Code
®
, Section 690-64(b) (2).
For installations in Canada, observe the applicable Canadian standards.
Position Description