SMA America, LLC 5 Electrical Connection
Installation Manual SB6-11TL-US-IA-en-13 35
Load Disconnection Unit
Install a separate miniature circuit-breaker for each inverter, in order that the inverter can be safely
disconnected under load. See the technical data (11"Technical Data",page70) for the maximum
permissible rating.
5.4.1 Connecting the AC Cables in the DC Disconnect
1. Open all AC and DC circuit breakers or load-disconnecting switches.
2. Open the main fuse in the fuse box.
3. Ensure that there is no voltage between the fuse output and the ground bar. Use a multimeter.
The voltage must be 0 V.
4. Open the DC disconnect as described in section 8.3"Opening the DC Disconnect",page58.
5. Remove a suitable knockout opening on the bottom side of the DC disconnect.
6. Lay a cable conduit from the fuse box to the DC disconnect (see chapter 5.2"Inserting the
Cables in the DC Disconnect",page31).
7. Lead the AC cable through the cable conduit from the inside of the fuse box into the inside of
the DC Disconnect.
Screw-type fuse elements as load disconnection unit
The Sunny Boy can be damaged during isolation under load.
Use a miniature circuit-breaker or listed switch-disconnector as load disconnection unit.
Do not use a screw-type fuse element as switch-disconnector.
Open terminals fully before insertion of the cables.
8. Connect the AC device grounding conductor to the
PE terminal labeled in the DC Disconnect.