5 Electrical Connection SMA America, LLC
34 SB6-11TL-US-IA-en-13 Installation Manual
System configuration
The following table shows the possible system configurations for the inverter types:
*not SB 11000TLUS-12
AC cable requirements
The cable must be dimensioned in accordance with the local and national directives for the
dimensioning of cables. The requirements for the minimum conductor cross-section derive from these
directives. Influencing factors for cable dimensioning are, among others, the following: nominal AC
current, type of cable, cable length, routing method, cable bundling, ambient temperature and
maximum desired line losses.
Inverter type Voltage
208 V WYE 240 V Split Phase
SB xxxxTLUS-10
SB xxxxTLUS-12 ✓ *
A neutral conductor must be connected to the inverter in either grid situation.
Only use solid wire or stranded wire
Do not use fine-wire strands.
Ambient temperature
The higher the ambient temperature, the higher the power losses.
Use cables with large cable cross-sections in installation sites with high ambient
temperatures.
Routing method
The cables heat up during operation. If there are several cables in a conduit, the temperature
of all cables increases.
Use cables with a large cross-section if you lay several cables in one conduit.
Position Name Value
A Conductor cross-section 6 to 2 AWG (16 to 35 mm²)
B Stripping insulation
3
4
in.(18 mm)