Sma SB 6000TL‑US Installation User Manual Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 92
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
5 Electrical Connection SMA America, LLC
40 SB6-11TL-US-IA-en-13 Installation Manual
5.5.1 DC Cable Requirements
DC cabling to the Combiner Box
Use copper wire that is rated for 10 to 6 AWG (6 to 16 mm²) and 194°F (90°C) (National
Electrical Code
®
690.35).
DC cabling Between the Combiner Box and the Inverter
Use copper wire that is rated for min. 8 AWG (10 mm²) and 194°F (90°C) (National Electrical
Code
®
690.35).
5.5.2 Connecting the DC Cables in the DC Disconnect
1. Lay a conduit from the Sunny Boy Combiner Box to the DC Disconnect
(see Section 5.2"Inserting the Cables in the DC Disconnect",page31).
2. Open the DC Disconnect as described in Section 8.3"Opening the DC Disconnect",page58.
3. Pull the DC cable from the Sunny Boy Combiner Box through the conduit into the DC Disconnect.
4. Connect the grounding conductor to terminal (B)
for the grounding conductor.
If necessary:
Connect the grounding cable of the PV frame to
terminal (A) for the grounding conductor.
Only use solid wire or stranded wire
Use the free of charge "Sunny Design" at www.SMA-America.com to design your PV
plant.
Open terminals fully before insertion of the cables.
Page view 39
1 2 ... 35 36 37 38 39 40 41 42 43 44 45 ... 91 92

Comments to this Manuals

No comments