7 Displays and Messages SMA America, LLC
50 SB6-11TL-US-IA-en-13 Installation Manual
PV overvoltage
Error message PV overvoltage.
1. Check the DC voltage at the DC Disconnect.
2. If the DC voltage is greater than 600 V: Contact the planner/installer of the PV array.
or
If the DC voltage is lower than 600 V: Connect the Sunny Boy to the PV array again as
described in Section 5.5"DC Connection",page39.
3. If the message occurs again, disconnect the Sunny Boy from the grid and contact SMA (see
Section 14"Contact",page90).
Damage to the inverter due to overvoltage
Disconnect the inverter from the PV array immediately.
!PV-Overvoltage!
!DISCONNECT DC!