SMA America, LLC 11 Technical Data
Installation Manual SB6-11TL-US-IA-en-13 87
11.9 Torque Values and Cable Sizes
*see National Electrical Code
®
, 310.16
in-lb. Nm Wire size
Sunny Boy
AC terminal block 40 4.5 6 to 2 AWG (16 to 35 mm²)
copper wire, rated for 194°F
(90°C)*
DC terminal block 40 4.5 8 to 2 AWG (10 to 35 mm²)
copper wire, rated for 194°F
(90°C) *
Attachment to the wall mounting
bracket
44 5 -
Enclosure lid 53 6 -
DC Disconnect
AC terminal block 40 4.5 6 to 2 AWG (16 to 35 mm²)
copper wire, rated for 194°F
(90°C)*
DC terminal block 40 4.5 8 to 2 AWG (10 to 35 mm²)
copper wire, rated for 194°F
(90°C) *
Terminal block grounding
conductor
40 4.5 8 to 2 AWG (10 to 35 mm²)
copper wire, rated for 194°F
(90°C) *
Attachment to the wall mounting
bracket
44 5 -
Enclosure lid 44 5 -