Sma SB 6000TL‑US Installation User Manual Page 28

  • Download
  • Add to my manuals
  • Print
  • Page
    / 92
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 27
5 Electrical Connection SMA America, LLC
28 SB6-11TL-US-IA-en-13 Installation Manual
5 Electrical Connection
High voltages on the AC and DC cables
Risk of death or serious injury due to electric shock.
Only connect the inverters as described in this manual.
Only electrically qualified persons may work on the inverter.
Ingress of moisture when mounting and installing the Sunny Boy
Potential damage to the Sunny Boy.
For inserting the conduits into the enclosure and the DC Disconnect, only use UL-certified
rainproof sleeves or waterproof sleeves that fulfill UL 514B.
Do not open the Sunny Boy in the event of rain or a high level of humidity (>95%).
Damage to the seal of the enclosure lid during frost
When opening the Sunny Boy during frost, the seal of the enclosure lid can be damaged. There may
be an ingress of moisture damaging the Sunny Boy.
Do not open the Sunny Boy when the outdoor temperature is below 23°F ( − 5°C).
Electrostatic discharges through touching component parts
Potential damage to the Sunny Boy.
Ground yourself before touching any electronic component.
Ground faults, unreliable and highly resistive connections due to Wire Nuts
®
Potential damage to or failure of the Sunny Boy.
•Do not use Wire Nuts
®
.
Electrical Installations
All electrical installations must be carried out in accordance with the electrical standards
applicable on-site and the National Electrical Code
®
ANSI/NFPA 70. Installations in Canada
must be carried out in accordance with the applicable Canadian standards.
Before connecting the inverter to the power distribution grid, contact your local electric utility
company. This connection may be made only by electrically qualified persons.
Page view 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 91 92

Comments to this Manuals

No comments