11 Technical Data SMA America, LLC
70 SB6-11TL-US-IA-en-13 Installation Manual
11 Technical Data
11.1 Sunny Boy 6000TL-US
PV Array Connection
Grid Connection
Maximum DC power 6,200 W
Maximum DC voltage 600 V
Minimum DC voltage at 208VAC 300 V
Minimum DC voltage at 240VAC 345 V
DC nominal voltage at 208VAC 345 V
DC nominal voltage at 240VAC 379 V
DC start voltage 360 V
MPP voltage range at 208 V AC 300 V to 480 V
MPP voltage range at 240 V AC 345 V to 480 V
Maximum DC input current at 208VAC 21 A
Maximum DC input current at 240VAC 18 A
Number of MPP trackers 1 (OptiTrac)
AC nominal power 6,000 W
Maximum AC power 6,000 W
Reduced power output at 140°F (60°C) 6,000 W
Maximum AC current at 208VAC 33 A
Maximum AC current at 240VAC 29 A
Maximum AC reverse current 0 A
Maximum AC fuse size 45 A
AC nominal voltage 208 V/240 V
AC voltage range at 208 V AC 183 V to 229 V
AC voltage range at 240 V AC 211 V to 264 V
AC nominal frequency 60 Hz
AC nominal frequency range 59.3 Hz to 60.5 Hz
Power factor at nominal power 1
Total harmonic factor < 4%
AC connection/Power Balancing Two Phases / ✓
Ground fault monitoring (R-Iso) Yes
Power consumption nighttime ≤ 0.25 W