AC Output
Feed-in phases 3
Connection phases 3
Inrush current of the internal power supply 48 A (100 ms)
* up to +5% I
max
possible at V
ac
<V
acnom
Efficiency
Maximum efficiency 98.6%
European weighted efficiency 98.4%
CEC weighted efficiency 98.5%
Protective Devices
DC overvoltage protection TypeI
Lightning protection as per IEC62305-1 Lightning protection levelIII
Surge arrester for auxiliary power supply Yes
Protection class in accordance with IEC 62103 I
Overvoltage category as per IEC 60664-1 III
General Data
Width x height x depth 2,562mmx2,272mmx956mm
Weight 1,900kg
Operating temperature range −25°Cto+62°C
Operating temperature range for low-temperature option −40°Cto+62°C
Noise emission at a distance of 10m 60db(A)
Self-consumption in operation < 1,900W
Standby consumption <100W
External supply voltage 230V/400V(3/N/PE), 50Hz/60Hz
Degree of protection of electronics IP54
Degree of protection of the connection area IP43
Maximum permissible value for relative humidity (non-
condensing)
15%…95%
Maximum operating altitude above mean sea level 2,000m
Maximum operating altitude above MSL for option "In-
stallation at high altitudes"
4,000m
Fresh air consumption 3,000m³/h
8 Technical Data
SMA Solar Technology AG
Operating Manual 53SCCPXT-IA-E4-en-44