Page 1 - SUNNY BOY 1.5 / 2.5

ServiceManualforInstallersSUNNY BOY 1.5 / 2.5SB15-25-SG-en-10 | Version 1.0ENGLISH

Page 2 - Table of Contents

4 Event MessagesEvent number Message, cause and corrective measures101 to 103Grid faultThe grid voltage or grid impedance at the connection point of t

Page 3 - Legal Provisions

Event number Message, cause and corrective measures301Grid faultThe ten-minute average value of the grid voltage is no longer within the per-missible

Page 4 - 1.4 Nomenclature

Event number Message, cause and corrective measures501Grid faultThe power frequency is not within the permissible range. The inverter has dis-connecte

Page 5 - 2 Safety

Event number Message, cause and corrective measures801Waiting for grid voltage > Grid failure > Check AC circuit breakerThe AC cable is not corr

Page 6 - 2.2 Safety Information

Event number Message, cause and corrective measures1302Waiting for grid voltage > Installation failure grid connection > Checkgrid and fusesL or

Page 7

Event number Message, cause and corrective measures3501Insulation failure > Check generatorThe inverter has detected a ground fault in the PV array

Page 8 - Connection

Event number Message, cause and corrective measures6501 to 6509Self-diagnosis > OvertemperatureThe inverter has switched off due to excessive tempe

Page 9

Event number Message, cause and corrective measures7329Condition test successfulThe testing of the update conditions was successful. The firmware upda

Page 10 - 4 Event Messages

Event number Message, cause and corrective measures7347Incompatible fileThe configuration file is not suitable for this inverter.Corrective measures:•

Page 11 - SMA Solar Technology AG

Event number Message, cause and corrective measures7355Update WebUIThe inverter is updating the inverter user interface.7356Update of the WebUI not su

Page 12

Table of Contents1 Information on this Document ... 41.1 Validity...

Page 13

Event number Message, cause and corrective measures8708Timeout in communication for active power limitationCommunication to the system control absent.

Page 14

Event number Message, cause and corrective measures9005Changing of grid parameters not possible > Ensure DC supply.This error can have the followin

Page 15

Event number Message, cause and corrective measures10250[Interface]: package error rate [ok / high]The package error rate has changed. If the package

Page 16

Event number Message, cause and corrective measures10254[Interface]: duplex mode goes to [Full / Half]The duplex mode (data transfer mode) has changed

Page 17

Event number Message, cause and corrective measures10286WLAN connection lostThe inverter has lost WLAN connection to the selected network.Corrective m

Page 18

5 Cleaning the InverterDamage to the inverter due to the use of cleaning agents• If the inverter is dirty, clean the enclosure, the enclosure lid, the

Page 19

6 Checking the PV System for Ground FaultsIf the inverter displays the event numbers 3501, 3601 or 3701, there could be a ground fault. Theelectrical

Page 20

Example: Location of the ground faultThe example shows a ground fault between the second and third PV module.3. If a definite ground fault cannot be m

Page 21

Calculating the insulation resistanceThe expected total resistance of the PV system or of an individual string can be calculatedusing the following fo

Page 22

7 Opening the InverterIf you have to open the inverter enclosure lid for repairs or replacement, proceed as described inthe following.Damage to the se

Page 23

Legal ProvisionsThe information contained in these documents is property of SMA Solar Technology AG. Anypublication, whether in whole or in part, requ

Page 24

8 Recommissioning the InverterRequirements:☐ The inverter must be correctly mounted.☐ The circuit breaker must be correctly rated.☐ All cables must be

Page 25 - 5 Cleaning the Inverter

9 Decommissioning the InverterTo decommission the inverter completely upon completion of its service life, proceed as describedin this Section.Risk of

Page 26 - Test by Measuring the Voltage

10 Spare PartsYou will find the spare parts for your product in the following overview. If required, these can beordered from SMA Solar Technology AG

Page 27

11 ContactIf you have technical problems with our products, please contact the SMAServiceLine. We needthe following information in order to provide

Page 28

South Africa SMA Solar Technology SouthAfrica Pty Ltd.Centurion (Pretoria)08600SUNNY(0860078669)International:+27(12)6223000ΕλλάδαΚύπροςKıbrısБъл

Page 30

SMA Solar Technologywww.SMA-Solar.com

Page 31

1 Information on this Document1.1 ValidityThis document is valid for the following device types from firmware version 2.0.1.R:• SB1.5-1VL-40 (Sunny Bo

Page 32 - 10 Spare Parts

2 Safety2.1 Disconnecting the Inverter from Voltage SourcesPrior to performing any work on the inverter, always disconnect it from all voltage sources

Page 33 - 11 Contact

7. Ensure that no voltage is present at the DCinputs on the inverter using a suitable measuringdevice.8. Loosen the swivel nuts.9. Loosen the screws o

Page 34 - 9:;*<+%,='3)>+%

Danger to life due to high voltages of the PV arrayWhen exposed to sunlight, the PV array generates dangerous DC voltage which is present in theDC con

Page 35

3 Calling Up the Inverter User Interface via DirectConnectionYou can call up the inverter user interface outside of a network via a direct connection

Page 36 - SMA Solar Technology

• Search for WLAN networks with your device.• Select the inverter SSID SMA[serial number].• Enter the inverter WLAN password. Within the first ten ope