SMA Solar Technology AG Failures and Warnings
User Manual SC-BEN092751 57
420
Error text:
ADAPSCP overtemperature
Error type 3
Cause:
Heatsink temperature is too high (hardware threshold).
Corrective measures:
Check function of the cooling fans of the inverter bridge.
Clean soiled air inlet or heatsink.
Ambient or cooling air temperature too high.
If this error occurs frequently, contact the Sunny Central Serviceline.
421
Error text:
ADAPSCP Overvoltage DC voltage link
Error type 2
Cause:
DC voltage is too high on the solar generator side (hardware threshold).
Corrective measures:
Immediately disconnect the solar generator from the Sunny Central! Risk of
damage to the Sunny Central!
•Check DC voltage.
Check module wiring and system design.