SMA Solar Technology AG Measurement Channels and Messages
User Manual SB_SMC-BEN092840 29
6.2 Status Messages
The inverters can be in various operating modes. These are displayed as status messages which can
vary according to the method of communication.
Vpv PV input voltage
Vpv-Setpoint PV target voltage
Zac Grid impedance
Message Description and corrective measure
Balanced The Sunny Mini Central has disconnected from the grid, or is limiting its output to
5 kVA over a 10-minute average. The Sunny Mini Central is part of a three-phase
system equipped with two further Sunny Mini Centrals and the SMA Power
Balancer to avoid unbalanced load. The "Balanced" message is displayed for the
following reasons:
Case 1:
The operating parameter "PowerBalancer" is set to "PhaseGuard". One of the three
Sunny Mini Central inverters in this system has indicated a grid fault and
disconnected from the grid. Consequently, the other two Sunny Mini Central
inverters also disconnect from the grid to avoid an unbalanced load, and send the
message "Balanced".
Case 2:
The operating parameter "PowerBalancer" is set to "PowerGuard". One of the
3 Sunny Mini Centrals in this system has detected a device or grid fault and
disconnected from the grid. The two remaining Sunny Mini Centrals reduce their
output over a 10-minute average to 5 kVA in order to prevent an unbalanced load.
Case 3:
The operating parameter "PowerBalancer" is set to "FaultGuard". One of the 3
Sunny Mini Centrals in this system has indicated a device or grid fault and
disconnected from the grid.
When grid failure occurs, the other two Sunny Mini Centrals also disconnect from
the grid to prevent an unbalanced load, and send the message "Balanced".
In the event of a device fault, the fault message is sent to the other two devices with
a time lapse of 5 minutes. After the 5 minutes have passed, the other two devices
disconnect from the grid and send the message "Balanced".
Measuring
channel
Description